Water Cooling And Heating Chiller

Water Cooling And Heating Chiller

-10C~ 80C Customized 10 Hp Water Cooling and Heating Chiller 1. Technical Design Requirements: 1. Compressed air temperature range: compressed air inlet temperature 30 ℃ -55 ℃, the export temperature range of 20 ℃ -60 ℃; 2. Compressed air flow 10m ³ / min, compressed air inlet and outlet...

Chat Now

Product Details

Water Cooling and Heating Chiller


1. Technical Design Requirements:

1. Compressed air temperature range: compressed air inlet temperature 30 ℃ -55 ℃, the export temperature range of 20 ℃ -60 ℃;

2. Compressed air flow 10m ³ / min, compressed air inlet and outlet diameter DN80-DN100; Compressed air pressure range 1bar-4bar;

3. Heating cycle ≤ 90 minutes; cooling cycle ≤ 90 minutes, heating 1-2 ℃ / min, cooling 1-2 ℃ / min;

4. Temperature control accuracy: ± 3 ℃;

5. Media tank maximum volume: 120L, tank material: 304 stainless steel plate welder, wall thickness: 1.5mm, insulation material: rubber fire insulation cotton;

6. Dielectric temperature range -10 ℃ -80 ℃; medium selection of ethylene glycol antifreeze, freezing point ≥ 20 ℃, viscosity ≤ 40mm ² / s;


2. Unit Overview

1. Compressor is fully enclosed scroll compressor, using the brand American Copeland.

2. Unit temperature control accuracy of ± 1 ℃, the water pressure provided by not less than 2bar.

3. Refrigeration system design multiple protection function, through the unit's control panel can determine the location of the fault.

4. The protection function of the hot and cold unit includes high and low pressure protection; safety valve; overheating protection; overload protection; reverse phase; lack of phase; water flow protection, failure to take the unit to stop alarm measures.


3.Water Cooling and Heating Chiller Tech Specifications:



heating and cooling chiller.jpg


Outlet Temp Control Range

                 

-10~80

Cooling Water Inlet/Outlet

                    

32/37

Cooling Capacityooling CapacityOutlet=0

Kw

 16.2

Kcal/h

13932

Compressor

Brand

Copeland

Type

Scroll

Protector

PTCPhaseOverload and so on

Quantity

2

Input Power

Kw

3.75*2

Rotary speed/Power

2950rpm/380V/50Hz

Oil Separator

Structure

External style

Separation accuracy

99.9%

Filter Material

Stainless Steel

Evaporator

Type

Plate Heat Exchanger

Material

304

Water Flow

m3/h

5.47

Pipe Size

mm

DN 40

Pressure

KPa

30-80

Temp Control

temperature sensor

Medium

antifreeze

Condenser

Type

Shell and Tubes

Material

Copper Pipe

Cylinder material

Q235B

Flow

m3/h

6.85

Water Pipe

mm

DN 40

Pressure

Kpa

40-100

Tank

Material

304

Insulated

Advanced waterproof fire insulation

Volume

120

Heating Capacity

Kw

12

Pump

inside

Material

SST

Power

Kw

0.75

Temp range

-20 to 95

Pump

Outside

Material

SST

Power

Kw

0.75

Temp range

-20 to 95

Dryer Filter

Type

Horizontal

Material

carbon

Filter

Alumina molecular sieve

Electric Control

Controller

Auto

Pump Control

Intelligent interlock control

Refrigerant

Control Way

Expansion Valve

Model

R22

Charge

KG

3.1+3.1

Other Specs

Exhaust Pressure

PA

12-16

Exhaust Temp

70-90

Ambient Temp

≤40

Running Current

A

41

Unit Weight

KG

490

Dimension

mm

See drawing

ANYDA is well acknowledged as one of the leading manufacturers of Water Cooling And Heating Chiller in China. All of the products for sale are made in our professional plant. Should you're interested in it, please be free to get the high-tech equipment with competitive price from us.
Previous:Water Chiller For Heating And Cooling Next:Injection Machine 3 In 1 Plastic Dehumidifying Dryer