Home Product Water Chiller Air Cooled Water Chiller
10000kcal/h Industrial Air Water Chiller

10000kcal/h Industrial Air Water Chiller

3Ton Small Modular Air Cooled Scroll Water Chiller Unit We supply 3Ton Small Modular Air Cooled Scroll Water Chiller Unit. We supplied all kinds of industrial chiller, we hope to establish long time business relationship with you. 3Ton Small Modular Air Cooled Scroll Water Chiller Unit...
Product Details

10000kcal/h Industrial Air Water Chiller


1.Simply Introduce

This 10000kcal/h air cooled water chiller system designed of case type, high durable and reliable,widely used in industrial processing machines,like plastics,extruding machines,beverage and so on.This series of working flow is based on the basic principle of heat exchange. It is applicable to the industry that requires flow of precisely controlled chilled water, and considered as indispensable equipment for modern industry.


2.Parameters 

Name

10000kcal/h Water Chiller

Model

AYD-05A

Cooling Capacity (kcal/h)

10000

Cold Water Flow(m3/h)

2.4

Air Volume( m3/h)

5300

Refrigerant

R22/R407C/R134A

Temp Control Scope(℃)

7-35

Compressor Input Power(KW)

3.75

Pump Power(KW)

0.75

Tank Volume(L)

40

The water pipe size (G")

1"

Power Supply

3N/380V/50HZ

Dimension(L×W×H)mm

1165*680*1540

Weight(KG)

250

Disposition:
1.Compressor:Sanyo;
2.Punp brand electronic board of micro computer
3.LG Exchange the contactor, LG heat relay,Carlo Phase;

Protective Device:                    
1.Phase protector
2.Fan overload protector
3.High/low voltage protector
4.Water level protector
5.Anti-freeze protector
Remarks:The cooling capacity of the model is calculated according to condenser temperature 45℃, evaporator temperature  2℃


3.Deailed Image

10000kcal water chiller


4.FAQ

1. How does a chiller system work?

Chiller has two circulation,one is process water circulation,the other is refrigerant gas circulation.Heat picked up from the process.Heat transfers to refrigerant circulation.Heat is remove to air or water.


2. How to calculate cooling capacity for chillers

Cooling Capacity(kw)= Flow Rate(m3/h)*Temp Change(T1-t2)/0.86

Heat Load= C(specific heat)* M(quality output per hour )*Temp Change(T1-T2)


3. Chiller capacity unit ?

1 kcal/h = 1.163W,1 W = 0.8598 kcal/h;

1 Btu/h = 0.2931W,1 W = 3.412 Btu/h;

1 USRT  = 3.517 kW,1 kW = 0.28434 USRT;

1 kcal/h = 3.968 Btu/h,1 Btu/h = 0.252 kcal/h;

1 USRT = 3024 kcal/h,10000 kcal/h = 3.3069 USRT;


4. Chiller maintenance?

Step 1: Keep Tubes Clean

Step 2: Ensure a Leak-free Unit

Step 3: Sustain Proper Water Treatment(prevent scale, corrosion)

Step 4: Analyze Oil and Refrigerant


5. Contact us:

anyda

Whatsapp:  86-13388382523

Skype: vivian418585

Wechat: vivian418585

Email: vivian@aydzl.com


ANYDA is well acknowledged as one of the leading manufacturers of 10000kcal/h air cooled scroll water chiller unit in China. All of the products for sale are made in our professional plant. Should you're interested in it, please be free to get the high-tech equipment with competitive price from us.

ANYDA is well acknowledged as one of the leading manufacturers of 10000kcal/h industrial air water chiller in China. All of the products for sale are made in our professional plant. Should you're interested in it, please be free to get the high-tech equipment with competitive price from us.
Hot Tags: 10000kcal/h industrial air water chiller China, manufacturers, plant, price, for sale
Send Inquiry